– As a guide-line, strands are manufactured to EN 61230:2008 Live Working. Portable equipment for earthing or earthing and short-ciruiting.
– PVC Insulation operating temperatures: -5°C – + 70°C.
– Supplied on wooden drums 300-500mt.
Available in bare strands or all translucent colours.
NOMINAL CROSS SECTION mm². | NOMINAL DIAM. OF BARE CONDUCTOR | NOMINAL PVC RADIAL THICKNESS | NOMINAL PVC OVERALL DIAMETER | MAX. RESISTANCE OF CONDUCTOR ohm/Km | SHORT CIRCUIT CURRENT FOR 1 SEC.(kA) |
16.00 | 5.7 | 1.3 | 8.4 | 1.210 | 1.9 |
25.00 | 7.1 | 1.3 | 9.8 | 0.780 | 3.5 |
35.00 | 8.8 | 1.4 | 11.4 | 0.554 | 5.1 |
40.00 | 9.2 | 1.6 | 12.5 | 0.480 | 6.0 |
50.00 | 10.1 | 1.8 | 13.8 | 0.386 | 7.5 |
70.00 | 12.2 | 1.8 | 15.8 | 0.272 | 11.9 |
95.00 | 14.2 | 2.0 | 18.2 | 0.206 | 14.7 |
120.00 | 16 | 2.0 | 20.1 | 0.161 | 20.4 |
190.00 | 18 | 2.0 | 22.00 | 0.129 | 25.5 |